个性化文献订阅>期刊> APPLIED ENERGY
 

A study of the reverse cycle defrosting performance on a multi-circuit outdoor coil unit in an air source heat pump - Part II: Modeling analysis

  作者 Qu, Minglu; Pan, Dongmei; Xia, Liang; Deng, Shiming; Jiang, Yiqiang  
  选自 期刊  APPLIED ENERGY;  卷期  2012年91-1;  页码  274-280  
  关联知识点  
 

[摘要]The experimental part of the study of the reverse cycle defrosting performance on a four-circuit outdoor coil unit in an experimental 6.5 kW heating capacity residential ASHP has been reported in Part I of a two-part series. The experimental results indicated that downwards flowing of the melted frost along a multi-circuit outdoor coil surface would have negative effects on defrosting performance. In order to quantitatively analyze the effects, this paper, the second part of the two-part series, reports on a modeling analysis where a semi-empirical model of the airside defrosting in the four-circuit outdoor coil unit was developed. The model was validated by comparing the predicted defrosting duration and temperature variation of collected melted frost with the corresponding experimental data presented in Part I of the two-part series. Using the validated model, the frost-melting rate and the temperature of melted frost on the surface of each circuit were predicted. The effects of the downwards flowing melted frost along the entire outdoor coil surface on defrosting performance were quantitatively analyzed. (C) 2011 Elsevier Ltd. All rights reserved.

 
      被申请数(0)  
 

[全文传递流程]